DTM8000
Digital Tachometer
Installation and Operating Manual
LT49 (A-5-3196A)
MN1327
Quick Jump
What models and recommended accessories are
available?
See page 3ꢀ
Looking for detailed specifications?
See page 3ꢀ
Want to get started fast?
See basic electrical hook-up details on page 5ꢀ
See mechanical installation details on page 4ꢀ
See some sample applications starting on page 15ꢀ
Need Help?
See troubleshooting on page 19ꢀ
LIMITED WARRANTY
Foraperiodofone(1)yearfromthedateoforiginalpurchase,BALDORwillrepairorreplacewithoutchargecontrols
and accessories which our examination proves to be defective in material or workmanship$ This warranty is valid if
theunithasnotbeentamperedwithbyunauthorizedpersons,misused,abused,orimproperlyinstalledandhasbeen
used in accordance with the instructions and/or ratings supplied$ This warranty is in lieu of any other warranty or
guaranteeexpressedorimplied$BALDORshallnotbeheldresponsibleforanyexpense(includinginstallationand
removal),inconvenience,orconsequentialdamage,includinginjurytoanypersonorpropertycausedbyitemsofour
manufacture or sale$ (Some states do not allow exclusion or limitation of incidental or consequential damages, so
theaboveexclusionmaynotapply$)Inanyevent,BALDORstotalliability,underallcircumstances,shallnotexceed
the full purchase price of the control$ Claims for purchase price refunds, repairs, or replacements must be referred
to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the
problem encountered$ No liability is assumed for expendable items such as fuses$
GoodsmaybereturnedonlywithwrittennotificationincludingaBALDORReturnAuthorizationNumberandanyreturn
shipments must be prepaid$
WARNING
Improper installation or operation of this control may cause injury to personnel or control failureꢀ The control must be
installedinaccordancewithlocal,state,andnationalsafetycodesꢀMakecertainthatthepowersupplyisdisconnected
before attempting to service or remove any components!!! If the power disconnect point is out of sight, lock it in
disconnected position and tag to prevent unexpected application of powerꢀ Only a qualified electrician or service
personnel should perform any electrical troubleshooting or maintenanceꢀ At no time should circuit continuity be
checked by shorting terminals with a screwdriver or other metal deviceꢀ
Table of Contents
Introduction ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ2
General Featuresꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ2
Models & Options ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Model Tableꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Recommended Accessories ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Specificationsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Electricalꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Mechanical ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Environmental ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3
Mechanical Installationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4
Exploded Panel View ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4
Cut-out and Mounting Dimensions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4
Electrical Installation & Diagrams ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5
P1 Terminal Block Wiring Diagram ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5
P1 Terminal Block Descriptions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5
Basic Operating Instructions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6
Rate, Time, and Counter Modes Explained ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6
Visual Reference ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6
How to Change a Parameter's Value (The Short Story) ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6
Operating the User Interface (The Long Story)ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6
Detailed Configuration Instructions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7
Factory Set Configurationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7
Resetting the Unit to Factory Settings ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7
JP1 (Program Enable Jumper)ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7
Software Parameters ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ8
Parameter Descriptions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ10
Application Examples ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ15
Pump Flow Monitor with Audible and Visual Alarm ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ15
Conveyor Oven Time Monitor with Over-Heating Alarm ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ16
Take-up / Pay-out Reel Material Measurement with Alarmꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ17
Bi-directional Incremental Position Display ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ18
Troubleshooting ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ19
Download from Www.Somanuals.com. 1All Manuals Search And Download.
Introduction
The DTM8000 Digital Meter is a powerful, microprocessor-based unit capable of being configured for
anumberoftodaysdemandingmeasurementneedsꢀItcanbequicklyconfiguredtooperateasadigital
rate meter, timer, or feature-filled process counterꢀ It also offers up to two alarm outputs which can be
adjustedforanumberoftriggerconditionsꢀ Itsdurable1/8DINaluminumhousingcanbeeasilymounted
in a panel or control cabinetꢀ Flexibility makes the DTM8000 ideal for applications such as:
Pay-out and Take-up Limit Monitors
Conveyor Oven Tunnel-Time Monitors
Rotating Machinery Tachometers
MaterialMeasurementMeters
General Features
- Microprocessor-based design combines responsiveness and accuracy in one package
- Selectable display update rate
- Capable of measuring shaft speeds lower than 1 RPM @ 1 pulse per revolution
- Large 4 digit, ½ LED display
- Field programmable via front-panel keypad
- Lexan membrane and gasket (which are included) meet NEMA 4X standards when used with NEMA
4X enclosures
- Internal program-enable jumper selectively prevents tampering with units configuration
- Universal power supply accepts line voltages inputs from 85-265VAC @ 50-60Hz without switches
or jumpersꢀ The unit automatically adjusts as neededꢀ
- Non-volatile memory stores adjustable parameters even when power has been removed
- Compatible with a variety of signal input types including: Hall-Effect Pickups, Photoelectric, TTL, etcꢀ
Note: Open collector devices must be capable of sinking 3mAꢀ
- Wide operating ambient temperature range of -10C to 45C (14F to 113F)
- Self-contained power supply for external sensor, limited to 5V @ 50mA
- Up to 2 programmable alarm outputs with Form C contacts rated to 250VAC @ 5A
- Multiple auto-ranging features allow the user to view display values from 0ꢀ001 to 99,990 in any user-
defined unitꢀ (GPH, MPH, RPM, etcꢀ)
- Multiple operating modes including:
Rate Mode Displays in rate unit such as RPM, Gallons per Second, etcꢀ
Time Mode Displays in time unit such as HH:MM, MM:SS, SS:TT, or other unit
Counter Modes Displays resettable and reloadable counter value which can optionally
increment or decrement for each input pulseꢀ Quadrature inputs can automatically
be translated to up/down counts for bidirectional applications
Download from Www.Somanuals.2com. All Manuals Search And Download.
Models & Options
Model Table
Quadrature
Encoder
Compatible?
Model
DTM8000-6
Input Voltage
Alarm
Outputs
Measures
Rate?
Measures
Time?
Up
Counter?
Down
Counter?
85-265VAC
1
Yes
Yes
Yes
Yes
Yes
RecommendedAccessories
Pulses per
Revolution
RPM Range When Used With
DTM8000
Model
Description
HPU10
RK60-56
RK60-145
Hall-Effect Pickup, Single Channel
Hall-Effect Pickup, Single Channel
Hall-Effect Pickup, Single Channel
10
60
60
0.1 – 10,000 RPM
0.02 – 1,600 RPM
0.02 – 1,600 RPM
Specifications
Electrical
Line Input Voltage----------------------------------------------------------------------------------Any Voltage from 85-265 VAC
Line Input Frequency--------------------------------------------------------------------------------- Any Freq. from 48-62 Hertz
Signal Input Frequency Range----------------------------------------------------------------- 0 – 100,000 Pulses per Minute
(Higher frequencies are possible when using internal frequency divisor)
Display Range--------------------------------------------------------------------------------------------------------- 0.001 – 99,990
Units of Operation----------------------------------------------------------------------------------User Programmable, any Unit
Sensor / Pickup Power Supply-----------------------------------------------------------------------------------------5V @ 50mA
Isolated Alarm Relay Output Ratings ------------------------------------------------------------------------------240VAC @ 5A
Mechanical
Display Type ---------------------------------------------------------------------------------------------LED, Red, 4 Digit, ½” Height
Housing Type (with supplied gasket in NEMA 4X panel)-------------------------------------------------------------- NEMA 4X
Connector Style -----------------------------------------------------------------------------------12-position 5mm European Style
Terminal Block Torque Setting ------------------------------------------------------------------------------ 4.4 in. lb. Max or .5Nm
Faceplate Material--------------------------------------------------------------------------Polycarbonate with GE Lexan Overlay
Housing Material ----------------------------------------------------------------------------------------------------------------- Aluminum
Length (Required Panel Depth) ----------------------------------------------------------------------------------- 4.625", 117.48mm
Faceplate Width ------------------------------------------------------------------------------------------------------ 4.539", 115.29mm
Weight ------------------------------------------------------------------------------------------------------ .8425 lb, 13.48 oz, 382.14g
Environmental
Operating Temperature Range------------------------------------------------------------------------10C to 45C (15F to 115F)
Operating Humidity Range--------------------------------------------------------------------------------- 95%, non-condensing
Download from Www.Somanuals.com. 3All Manuals Search And Download.
Mechanical Installation
Exploded Panel View
PANEL MOUNTING GASKET
(WITH THE ADHESIVE SIDE OF
GASKET FACING THE CUSTOMER
MOUNTING PANEL)
CUSTOMER
MOUNTING PANEL
(HOLE CUT-OUT FOR CONTROL
HOUSING APPROXIMATELY
3.622" WIDE BY 1.770" HIGH)
DTM8000 SERIES
TACHOMETER
SUPPLIED WITH EACH CONTROL:
1) GASKET
2) (2) 6-32 X 3/4 PANHEAD BLACK OXIDE STAINLESS SCREWS
3) (2) #6 NUT WITH LOCKWASHER
Cut-out and Mounting Dimensions
4.000"
5.000"
ENTER
2.289"
1.656"
TACHOMETER
4.000"
4.625"
3.622
"
DTM8000-6
HOUSING DEPTH
4.625"
0.885"
1.770"
.140 x 2
"
PANEL CUT-OUT
Download from Www.Somanuals.4com. All Manuals Search And Download.
Electrical Installation & Diagrams
P1 Terminal Block Wiring Diagram
NC2
C2
Alarm Output 2 - Normally Closed
Alarm Output 2 - Common
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
Form C Relay Output (Programmable)
}
NO2
NC1
C1
Alarm Output 2 - Normally Open
Alarm Output 1 - Normally Closed
Alarm Output 1 - Common
Alarm Output 1 - Normally Open
AC NEUTRAL
Form C
Relay Output
DTM8000-6
HOOK-UP
}
NO1
N
(Programmable)
AC LINE INPUT
L
2 Amp
85-265VAC
AC LINE
}
AC LINE INPUT
PICK-UP
MOUNTED
COM
+5V
S1
black
red
COMMON
+5VDC
P1-9
P1-10
P1-11
P1-12
white
SIGNAL 1
SIGNAL 2
S2
*
* Used for various functions, including quadrature counter mode.
P1 Terminal Block Descriptions
P1-1 (2NC) This is the normally-closed contact of the second user assignable relay outputꢀ
P1-2 (2C) This is the common contact of the second user assignable relayꢀ
P1-3 (2NO) This is the normally-open contact of the second user assignable relay outputꢀ
P1-4 (1NC) This is the normally-closed contact of the first user assignable relay outputꢀ
P1-5 (1C) This is the common contact of the first user assignable relayꢀ
P1-6 (1NO) This is the normally-open contact of the first user assignable relay outputꢀ
P1-7 (AC / N) For single phase AC lines connect the Neutral side of your AC line to this terminalꢀ For
systems with two hot AC lines, connect either of the Hot AC lines to this terminalꢀ
P1-8 (AC / L) For single phase AC lines connect the Hot side of your AC line to this terminalꢀ For
systems with two hot AC lines, connect either of the Hot AC lines to this terminalꢀ
P1-9 (COM) This is the common point for the control logicꢀ The speed sensor common lead as well
as any other source needing to reference the control common will be connected to this terminalꢀ
P1-10 (+5V) This is a self-contained +5VDC power supply capable of up to 50mAꢀ The speed sensor
supply lead can be connected to this terminal for its power sourceꢀ
P1-11 (S1) This is the Signal input terminal for single channel operation or channel 1 of dual channel
operationꢀ The signal lead of your speed or counter sensor will be connected hereꢀ
P1-12 (S2) This is the Signal input terminal for channel 2 during dual channel operationꢀ The second
signal lead of the speed or position sensor should be connected hereꢀ This terminal is also used
as a reset input or function change input for various operations of the controlꢀ In counter modes,
this input may also be used as a counter reset or enable gateꢀ
Download from Www.Somanuals.com. 5All Manuals Search And Download.
Basic Operating Instructions
Rate, Time, and Counter Modes Explained
In Rate Mode, the DTM8000 measures the input frequency, converts it to the user-defined units, and
displays the rate in the display window of the user interfaceꢀ Most applications utilize rate mode and
display in units such as gallons-per-minute, feet-per-second, and RPMꢀ
In Time Mode, the DMT8000 measures the input frequency, converts it to the user-defined time units,
and displays the time in the display windowꢀ This mode is most-commonly used in time-sensitive
processes such as conveyor ovens and plating applicationsꢀ
In Counter Modes, the DTM8000 counts each incoming pulse, scales it per the user-defined ratios, and
displays the count in the display windowꢀ Typical counting applications include linear material
measurement, cycle counters, and liquid volume measurementꢀ
VisualReference
ENTER (Select) Button
ENTER
TACHOMETER
Up & Down Buttons
Display Window
How to Change a Parameter's Value (The Short Story)
1ꢀ Hold down the Enter button until Parameter-Selection Mode is entered
2ꢀ Using the Up and Down buttons, select the desired parameter number to view or edit
3ꢀ Press the Enter button to change the value of the parameter
4ꢀ Using the Up and Down buttons, change the parameter's value as desired
5ꢀ Press the Enter button to permanently save the changes (Return to Parameter-Selection Mode)
6ꢀ Select parameter zero and press the Enter button to return to Running Mode
Operating the User Interface (The Long Story)
The LED display has three basic operating modes: Running Mode, Parameter-Selection Mode, and
Value Modeꢀ Each of the three modes have specific visual indicators that allow the user to immediately
determine the current state or mode of the user interfaceꢀ Parameter-Selection Mode and Value
Mode can only be entered if the Program Enable jumper is in the On positionꢀ
Download from Www.Somanuals.6com. All Manuals Search And Download.
Running Mode is the default display of the unit when power is appliedꢀ In Running Mode, the display
shows the measured value in the appropriate user-defined format of rate, time, or countꢀ As the input
signal changes, the display is continuously updated to show the latest measurementꢀ In this display
mode, the Up and Down buttons serve no function other that to reset or silence alarms if configured
accordinglyꢀ Example displays for rate, time, and count operating modes are 13ꢀ60, 45:30, and 9301ꢀ
Parameter-Selection Mode can be entered by simply pressing and holding the Enter button down for
three secondsꢀ Once in Parameter-Selection Mode, the far left of the display will be a Pꢀ The right side
of the display will indicate the currently selected parameter number for editing purposesꢀ Pressing the
Up or Down button will increase or decrease the selected parameter number on the displayꢀ Although
the parameter numbers are in numerical order, some numbers are skippedꢀ These numbers represent
reserved parameters that are not displayedꢀ Once the desired parameter number is displayed, a press
of the Enter button will change the display to the Value Modeꢀ When in Parameter-Selection Mode,
pressing the Enter button with parameter 0 selected will cause the unit to return to Running
Modeꢀ Example displays for Parameter-Selection Mode are P 1, P 11, and P 54ꢀ
Value Mode is used to modify the value of the selected parameterꢀ When in Value Mode, the two dots
which form the colon, between digits two and three, will alternately flash (one, then the other) to inform
the user that a parameters value is being editedꢀ Pressing the Up or Down button increases or
decreasestheselectedparametersvalueꢀ Valuechangestakeeffectimmediatelyꢀ Forexample,when
scrolling through the alarm output conditions, the relay will activate as the always-active selection is
passedꢀ Once the desired value is showing in the display window, pressing the Enter button again will
return to Parameter-Selection Modeꢀ The new value is not saved in permanent memory until the Enter
button is pressedꢀ Removing power from the unit while in Value Mode may result in the specified new
value being lostꢀ
Detailed Configuration Instructions
Factory Set Configuration
When shipped from the factory, the following basic settings are in place:
Rate Mode Operation in RPM
S1 Signal Input Pulses-per-Revolution: 10
Decimal Point Display: Off
Auto-Ranging: Disabled
Alarm Output(s): Disabled
Resetting the Unit to Factory Settings
The factory settings can be easily restored using either of two methodsꢀ Both methods require the
Program Enable jumper to be in the On positionꢀ The first is to apply power to the unit with both the
Enter and Down buttons pressed for 3 secondsꢀ The second is to change the value of parameter 95
to 5ꢀ
JP1 (Program Enable Jumper)
The JP1 jumper is located under the dust cover on the back end of the upper boardꢀ When the jumper
is set to the "Off" position, all programming features are locked out to the front panel userꢀ When the
jumper is in the "On" position, the programming parameters are open to changeꢀ JP1 is shipped from
the factory set in the "On" positionꢀ
Download from Www.Somanuals.com. 7All Manuals Search And Download.
Software Parameters
Value Range
(units)
Factory
Settings
n/a
User
Parameter
Description
Settings
0
Selecting this item exits to Running Mode
n/a
Read-Only Parameters
Model Number
1
2
3
4
5
n/a
80
n/a
n/a
n/a
n/a
Software Build
1 – 9999
1 – 9999
n/a
Hardware Version
Serial Number – Major (reserved)
Serial Number – Minor (reserved)
n/a
General Setup
10
Operating Mode
1 – Rate Mode
1
2 – Time Mode
3 – Up Counter
4 – Down Counter
5 – Up / Down Counter
0 – 31 (Dim – Bright)
1 - Every Rising Edge
2 – Every Falling Edge
3 – Falling Edge / 4
4 – Falling Edge / 16
1 – Reset Disabled
2 – Reset on Keypress
3 – Reset on S2 Low
4 – Reset on S2 High
11
14
Display Intensity
20
1
Input Trigger / Prescaler Setup
16
Counter Mode Reset Configuration
1
Signal Input #1 (S1) Setup
Display Reference
Reference RPM
20
21
22
23
1 – 9999 (Display Units)
1 – 9999 (RPM)
1000
1000
10
Pulses Per Revolution
Recovery Rate
1 – 9999 (PPR)
0 – 1000 (1/2 seconds)
0 – Disabled
10
> 0 – Recovery 1/2 seconds
0 – 60 (seconds)
0 – Disabled
24
25
Display Smoothing / Averaging
Decimal Point Position
1
0
> 0 – Averaging Seconds
0 – DP Disabled (XXXX)
1 – X.XXX
2 – XX.XX
3 – XXX.X
4 – XXXX.
26
Auto-Ranging Configuration
0 – Auto-Ranging Off
1 – Auto-Range on Overflow
2 – Auto-Ranging On
0 – 9999 (counts)
0
0
27
30
31
32
33
34
35
36
37
Counter Mode Reset / Preload Value
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Counter Gate Configuration
1 – Disabled
1
2 – Counting Enabled (Low)
3 – Counting Enabled (High)
Download from Www.Somanuals.8com. All Manuals Search And Download.
Software Parameters, cont'd
Value Range
(units)
Factory
Settings
User
Parameter
Description
Alarm Output #1 Configuration
Activation Conditions
Settings
40
0 – Always Off
0
1 – Always On
2 – Active when Above
3 – Active when Below
4 – Active inside Range
5 – Active outside Range
1 – Constant & Auto Reset
2 – Constant & Manual Reset
3 – Pulsed & Auto Reset
4 – Pulsed & Manual Reset
1 – No Sil., Reset on Key
2 – No Sil., Reset on S2 High
3 – No Sil., Reset on S2 Low
4 – Sil., Reset on Key
41
42
Output Style & Reset Mode
Reset Configuration
1
1
5 – Sil., Reset on S2 High
6 – Sil., Reset on S2 Low
0 – Alarm Flash Disabled
1 – Alarm Flash Enabled
1 – 3600 (seconds)
43
Display Flash On Active Alarm
0
44
45
46
47
48
Pulse on Time
Pulse off Time
Pulse Count
Lower Limit
1
1
1 – 3600 (seconds)
0 – 9999 (pulses)
0
0 – 9999 (display units)
0 – 9999 (display units)
0
Upper Limit
9999
Alarm Output #2 Configuration
50
Activation Conditions
0 – Always Off
0
1 – Always On
2 – Active when Above
3 – Active when Below
4 – Active inside Range
5 – Active outside Range
1 – Constant & Auto Reset
2 – Constant & Manual Reset
3 – Pulsed & Auto Reset
4 – Pulsed & Manual Reset
1 – No Sil., Reset on Key
2 – No Sil., Reset on S2 High
3 – No Sil., Reset on S2 Low
4 – Sil., Reset on Key
5 – Sil., Reset on S2 High
6 – Sil., Reset on S2 Low
0 – Alarm Flash Disabled
1 – Alarm Flash Enabled
1 – 3600 (seconds)
51
52
Output Style
1
1
Reset Configuration
53
Display Flash On Active Alarm
0
54
55
56
57
58
Pulse On Time
Pulse Off Time
Pulse Count
Lower Limit
1
1
1 – 3600 (seconds)
0 – 9999 (pulses)
0
0 – 9999 (display units)
0 – 9999 (display units)
0
Upper Limit
9999
Parameter Memory Commands
95
98
99
Restore to Factory Settings
0 – Do Nothing & Exit
5 – Restore Factory Settings
0 – Do Nothing & Exit
5 – Save Setting
0
0
0
Save to User Setting Area
Restore from User Setting Area
0 – Do Nothing & Exit
1 – Restore Settings
Download from Www.Somanuals.com. 9All Manuals Search And Download.
Parameter Descriptions
Parameter 0 Exit to Running Mode
Whenparameter0isselectedinParameter-SelectionMode,theunitwillreturntoRunningMode
and display the running valueꢀ This should be selected once changes to parameters are
completedꢀ
Parameter 1 Model Number (Read Only)
This is a number which represents the base model number for the productꢀ For the DTM8000,
the model code is 80ꢀ
Parameter 2 Software Build (Read Only)
The software build is a code which identifies the software version of the unitꢀ
Parameter 3 Hardware Version (Read Only)
The hardware version is a code which identifies which hardware was used to build the unitꢀ
Parameter 4 & 5 Serial Number, Major & Minor (Read Only)
These parameters are reserved for future use as an electronic serial number and are unique to
each manufactured unitꢀ
Parameter 10 Operating Mode
This parameter defines the basic mode of operation for the entire unitꢀ It determines if the unit
is measuring rate, time, or count informationꢀ The following modes are available:
Mode 1 Rate Mode
Rate mode displays measurements in rate units such as RPM, Gallons per Hour, or Feet
per Secondꢀ
Mode 2 Time Mode
Time mode displays measurements in time units using the format AA:BBꢀ By default
AA:BB represents minutes (AA) and seconds (BB)ꢀ Optionally, it can be configured to
represent hours(AA)andminutes(BB)orotheruser-definedunitswitha1:60relationshipꢀ
Mode 3 Up Counter
Counter modes (3 5), display measurements in pulse counts or user-defined units which
are proportional to pulse countꢀ In these modes, the DTM8000 will count the pulses which
are applied to the S1 input and display the related valueꢀ In this mode, each input pulse
increments the counterꢀ
Mode 4 Down Counter
Same as Mode 3 above except each input pulse decrements the counterꢀ
Mode 5 Up / Down Counter
Same as Mode 3 above except each input pulse either increments or decrements the
counter depending upon the state of Signal Input #2 (S2)ꢀ If S2 is tied to common, the
counter is incremented; otherwise, it is decrementedꢀ
Parameter 11 Display Intensity
This parameter adjusts the intensity of the LED display digits in the front panel of the unitꢀ The
values of 0 31 correspond to a gradual change from very dim to very brightꢀ This is often useful
when used in the same panel as other pieces of equipment with LED displays and a uniform
display brightness is desiredꢀ
Parameter 14 Input Triggers / Prescale
This parameter determines how the S1 signal input is processedꢀ It specifies which signal edge
is used for the measurements and the value of the internal frequency divider or prescalerꢀ
Modes 3 and 4 should only be used if the input pulse rate exceeds the unit's maximum native
pulse rate (see specifications for details); otherwise, timing and counting calculations may
become sluggish and unnecessarily inaccurateꢀ
Mode 1: Every Rising Edge, No Prescaler
In this mode, the signal input is measured at every rising edgeꢀ
Mode 2: Every Falling Edge, No Prescaler
In this mode, the signal input is measured at every falling edgeꢀ
10
Mode 3: Falling Edge, Prescaler = 4
Inthismode,thesignalinputismeasuredatevery4thfallingedgeꢀ Thismodeisespecially
useful when the signal input frequency is beyond the native pulse-per-minute range of the
DTM8000ꢀ Because unit will automatically compensates for the prescaler, there is no
need to factor in the prescaler value when setting the Display and RPM Reference
parametersꢀ
Mode 4: Falling Edge, Prescaler = 16
Same as Mode 3 except the signal input is only measures every 16th falling edgeꢀ
Parameter 16 Counter Reset Configuration
In counter applications, it is often desirable to have the user or an external signal reset the
counter value to zero or some predetermined valueꢀ This parameter specifies which actions
will cause the counter to reset to the Counter Reset / Preset Value, parameter 27ꢀ
Mode 1: Reset Disabled
The counter cannot be resetꢀ
Mode 2: Reset On Button Press
The counter will reset to the Counter Reset / Preset Value, parameter 27, when any of the
user-interface buttons are depressedꢀ
Mode 3: Reset On S2 Input Low (Wired To Common)
The counter will reset to the Counter Reset / Preset Value, parameter 27, when S2 (signal
2) is brought to an electrically low state or wired to the unit's commonꢀ
Mode 4: Reset On S2 Input High (Not Wired To Common)
The counter will reset to the Counter Reset / Preset Value, parameter 27, when S2 (signal
2) is brought to an electrically high state (+5V) or left to float disconnected from the unit's
commonꢀ
Parameter 20 Signal Input 1 (S1) Display Reference
This is the number to be displayed when at the user-specified motor Reference RPMꢀ In Rate
Mode, this value represents the numerator of the rate unit such as feet, ounces, or revolutionsꢀ
In Time Mode, this value represents the reference time measured in seconds or minutesꢀ If the
desireddisplayisHH:MM,thenallvaluesshouldbeenteredinminutesꢀ IfMM:SSisdesired,then
all values should be entered in secondsꢀ In Counter Modes, this value is the reference count
ratio which corresponds to the number of counts which equate to the specified number of
reference pulses, parameter 21ꢀ See applications for examplesꢀ
Parameter 21 Signal Input 1 (S1) Reference RPM (Reference Pulses in Counter Modes)
This is the reference RPM at which the Display Reference value should be displayedꢀ In Rate
and Time Modes, this value represents the RPM of the encoder to which the Display Reference
correspondsꢀ In Counter Modes, this value is the Reference Pulses which correspond the the
specified number of displayed counter, parameter 21ꢀ See applications for examplesꢀ
Parameter 22 Signal Input 1 (S1) Pulses per Revolution
This is the number of pulses per revolutionꢀ Value may be from 1 to 9999ꢀ
Parameter 23 Signal Input 1 (S1) Recovery Rate
This is the rate at which the display will attempt to recover once the pulse train appears to have
stoppedꢀ The recovery rate is the number of half seconds which the unit will wait before dividing
(Rate Mode) or multiplying (Time Mode) the display value by 2 in an attempt to accurately
represent the current speed or timeꢀ In the absence of input pulses, this will continue at regular
intervals until either 0 (Rate Mode) or 99:99 (Time Mode) is reachedꢀ Setting this parameter to
0 will disable the automatic recovery featureꢀ If this parameter is set too low for the application,
thedivisionormultiplicationmayprematurelyoccurcausingthereadingtoreadtoohigh,toolow,
or unstableꢀ This can easily be corrected by simply increasing this parameter's value or
disabling it by setting it to zeroꢀ
Parameter 24 Signal Input 1 (S1) Display Smoothing / Averaging
This is the amount of time, in 1-second increments, which will be averaged before updating the
displayꢀ Setting this parameter to 0 will disable the averaging featureꢀ
11
Parameter 25 Signal Input 1 (S1) Decimal Point (DP) Position
Thisselectstheformatofthedisplaywithrespecttothedecimalpointspositionꢀ Thisparameter
does not effect the value entry for other parametersꢀ For example, it the user desires to display
10ꢀ00 at an input of 300RPM, then parameter 20 would be set to 1000, parameter 21 would be
set to 300, and parameter 25 would be set to 2ꢀ
Mode 0: Fixed XXXX
Mode 1: Fixed XꢀXXX
Mode 2: Fixed XXꢀXX
Mode 3: Fixed XXXꢀX
Mode 4: Fixed XXXXꢀ
Parameter 26 Signal Input 1 (S1) Auto-Ranging Configuration
This selects how the unit auto-ranges and formats the numbers for the displayꢀ
Mode 0: Auto-Ranging Disabled
The auto-ranging mode is disabledꢀ Ignoring decimal points, this limits the units display
range from 0 to 9999ꢀ Values beyond this range will display as an overflow error (-OF-)ꢀ
Mode 1: Auto-Ranging On Overflow Only
In this mode, auto-ranging will only be activated if the display value exceeds the maximum
native display valueꢀ For example, in XXꢀXX decimal point mode, 99ꢀ99 would be the
maximum native value for a 4-digit displayꢀ When the display is in overflow, it will display
only the 4 most significant digits and the decimal point will flashꢀ
Mode 2: Auto-Ranging Always Active
Inthismode,auto-rangingisalwaysactiveandcontinuouslyattemptstodisplaythe4most
significant digitsꢀ For example, the display will automatically range from 0ꢀ001 to 9999 as
neededꢀ In this mode, any value over 9999 will be displayed as an overflow error (-OF-)ꢀ
Parameter 27 Counter Reset / Preset Value
Thisisthevaluethatwillautomaticallybeloadedintothedisplayafterthecounterhasbeenresetꢀ
See Counter Reset Configuration, parameter 16, for more detailsꢀ
Parameter 30, 31, 32, 33, 34, 35, and 36
Reserved For Future Useꢀ
Parameter 37 Signal Input 2 (S2) Counter Gate (Enable / Disable) Configuration
This selects how the S2 input is utilized in single channel counter modesꢀ
Mode 1: Disabled (Required For Up / Down Counter Mode)
The S2 input will not function as a gate control and instead will act as the second input for
dual-channel counter operationꢀ
Mode 2: Counting Enabled When S2 Input Low (Wired To Common)
The unit will continue to count input pulses as long as the S2 is in an electrically low state
or connected to the unit's common terminalꢀ When the S2 input goes high (+5V) or is
allowed to float disconnected, the counter will be frozen at its current valueꢀ
Mode 3: Counting Enabled When S2 Input High (Not Wired To Common)
The unit will continue to count input pulses as long as the S2 is in an electrically high (+5V)
state or allowed to float disconnectedꢀ When the S2 input goes low or is wired to the unit's
common, the counter will be frozen at its current valueꢀ
Parameter 40 & 50 Alarm 1 & 2 Conditions
This defines which conditions will result in the alarm 1 or alarm 2 outputs being activatedꢀ
Mode 0: Always Inactive
The alarm output will remain in an inactive stateꢀ In this state, the NC and C contacts will
be internally electrically connectedꢀ
Mode 1: Always Active (When Power Is Applied)
The alarm output will become active when the power is applied to the unitꢀ In this state,
the NO and C contacts will be internally electrically connectedꢀ
Mode 2: Active When Display Value Above Limit
The alarm output will activate when the displayed value is above the upper limit settings,
parameters 48 and 58 accordinglyꢀ
12
Mode 3: Active When Display Value Below Limit
The alarm output will activate when the displayed value is below the lower limit settings,
parameters 47 and 57 accordinglyꢀ
Mode 4: Active When Display Value Inside Range
The alarm output will activate when the displayed value is greater than or equal to lower
limit settings and less than or equal to the upper limit settingꢀ
Mode 5: Active When Display Value Outside Range
The alarm output will activate when the displayed value is less than the lower limit setting
or greater than upper limit settingꢀ
Parameter 41 & 51 Alarm 1 & 2 Output Style & Reset Configuration
This setting configures the output mode and reset method for the alarm outputsꢀ
Mode 1: Constant & Auto Reset
In this mode, the alarm output will remain active until the alarm condition ceases to existꢀ
The alarm will automatically reset when the conditions return to normalꢀ
Mode 2: Constant & Manual Reset
In this mode, the alarm output will remain active until the alarm is reset manuallyꢀ See
parameters 42 and 52 for detailsꢀ
Mode 3: Pulse & Auto Reset
Inthismode, thealarmoutputwillpulseonandoffuntilthealarmconditionceasestoexistꢀ
The pulsed modes are commonly used for audible alarms where a constant output would
be considered distracting or awkwardꢀ The alarm will automatically reset when the
conditions return to normalꢀ
Mode 4: Pulse & Manual Reset
In this mode, the alarm output will pulse on and off until the alarm is reset manuallyꢀ See
parameters 42 and 52 for reset detailsꢀ The pulsed modes are commonly used for audible
alarms where a constant output would be considered distracting or awkwardꢀ
Parameter 42 & 52 Alarm 1 & 2 Reset Configuration
This setting determines which actions will cause an active alarm to be silenced or resetꢀ
Mode 1: No Silencing, Reset On Any Button Press
In this mode, an active alarm cannot be silencedꢀ Once the alarm condition ceases to
exist, however, any user-interface button may be pressed to cause a manual resetꢀ
Mode 2: No Silencing, Reset On S2 Input High (Not Wired To Common)
Similar to Mode 1ꢀ Once the alarm condition ceases to exist, setting the S2 input to a high
(+5V) state or allowing it to float disconnected will cause a manual resetꢀ
Mode 3: No Silencing, Reset On S2 Input Low (Wired To Common)
Similar to Mode 1ꢀ Once the alarm condition ceases to exist, setting the S2 input to a low
(COM) state or wiring it to common will cause a manual resetꢀ
Mode 4: Silencing Enabled, Reset On Any Button Press
When the conditions for an active alarm persist, pressing any user-interface button will
result in the alarm being silenced or deactivated, but not resetꢀ A second attempt to reset
the alarm must be made after the condition cease to exist to clear the alarmꢀ
Mode 5: Silencing Enabled, Reset On S2 Input High (Not Wired To Common)
Similar to Mode 4ꢀ Setting the S2 input to a high (+5V) state or allowing it to float
disconnected will cause the alarm to be silenced or reset depending on the current state
of the alarm conditionsꢀ
Mode 6: Silencing Enabled, Reset On S2 Input Low (Wired To Common)
Similar to Mode 4ꢀ Setting the S2 input to a low (COM) state or wiring it to common will
cause the alarm to be silenced or reset depending on the current state of the alarm
conditionsꢀ
Parameter 43 & 53 Alarm 1 & 2 Display Flash On Alarm
This will cause the display to flash when an alarm conduction is activeꢀ
Parameter 44 & 54 Alarm 1 & 2 Pulse on Time
This parameter defines the number of seconds the output should be enabled during the on
phase of an active pulsing alarms outputꢀ See application samples for examplesꢀ
13
Parameter 45 & 55 Alarm 1 & 2 Pulse off Time
This parameter defines the number of seconds the output should be disabled during the off
phase of an active pulsing alarms outputꢀ
Parameter 46 & 56 Alarm 1 & 2 Pulse Count
This setting determines how many pulses are output when the alarm is activated and is
configuredinpulseoutputstyleꢀWhen0isentered,theunitwillbesetforcontinuouspulseswhile
the alarm is activeꢀ
Parameter 47 & 57 Alarm 1 & 2 Lower Limit
Thissettingdefineseitherthelowerlimitorlowerendofarangeforthealarmregionꢀ Alarmlimits
are set in display units without regard to decimal point or colon positionꢀ In Rate and Counter
Modes, a limit of 123 could represent a display value of 123, 12ꢀ3, 1ꢀ23, or 0ꢀ123ꢀ When in Time
Mode, a limit of 123 would represent 1:23 on the displayꢀ
Parameter 48 & 58 Alarm 1 & 2 Upper Limit
This setting defines either the upper limit or upper end of a range for the alarm regionꢀ Alarm
limits are set in display units without regard to decimal point or colon positionꢀ In Rate and
CounterModes, alimitof123couldrepresentadisplayvalueof123, 12ꢀ3, 1ꢀ23, or0ꢀ123ꢀ When
in Time Mode, a limit of 123 would represent 1:23 on the displayꢀ
Parameter 95 Factory Settings Command
When set to a value of 5, the unit will be reset to factory settingsꢀ This can also be achieved by
applying power to the unit with both the Enter and Down buttons depressedꢀ The programming
jumper must be in the "On" position for this method to functionꢀ
Parameter 98 Save to User Settings Area Command
When set to a value of 5, the unit will store all adjustable parameters to the user settings areaꢀ
The user settings area is intended to be a location where a user can store settings specific to
their applicationꢀ A user can easily refresh their custom settingsꢀ Another common use for this
area is testing and initial setupꢀ The user can store known-good settings here and easily
experiment without the fear of losing the optimal configurationꢀ
Parameter 99 Restore from User Settings Area Command
Whensettoavalueof1, theunitwillrestorethealladjustableparametersfromtheusersettings
areaꢀ See parameter 98 for additional informationꢀ
14
Application Examples
Pump Flow Monitor with Audible and Visual Alarm
Description:
A pump monitor which displays the pump rate in gallons per minute with an audible and visual
alarm output which will warn the operator of excessively low flow conditions under 5ꢀ00 GPMꢀ
The alarm should not be able to be silenced and should be reset when any front-panel button is
pressedꢀ The display should indicate in the format xxꢀxx (GPM)ꢀ Due to normal fluctuations in
flow rates, it is desirable to have the display filter or average the value over 3 seconds to produce
a more accurate and steady displayꢀ
Application Diagram:
Motor Control
Fluid
Outlet
Encoder
Fluid
Inlet
Pump
ENTER
36.24
TACHOMETER
Pump Specs:
53 Shaft Rotations = 3 Gallons
DTM8000 Meter
Audible
Annunciator
Wiring Diagram:
NC2
C2
Not Used
Not Used
Not Used
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
NO2
NC1
C1
120VAC
Audible
Not Used
Annunciator
NO1
N
DTM8000-6
2 Amp
AC Line Input 85-265VAC, 50-60 Hz
L
}
COM
+5V
black
P1-9
red
P1-10
P1-11
P1-12
S1
S2
white
Not Used
Encoder
Parameter Configuration:
Parameter
Value
Notes
Rate Mode Setting (GPM is a rate-based unit)
10
20
21
22
24
25
40
41
42
43
47
1
300
53
10
3
Display should indicate 3.00 GPM (300) when motor at Reference RPM, parameter 21
This is the RPM at which the Display Reference, parameter 20, should be displayed
Pulses per revolution of shaft encoder or pickup is 10 PPR
Display filtering / averaging set to 3 seconds
2
Decimal point position set to XX.XX on display
3
Alarm active when display value is below lower limit
Constant alarm output with manual reset required
2
1
No silencing, reset on any button press
1
Flash display when alarm is active
500
Lower limit setting for 5.00 GPM (500). Limits are entered without regard for decimal
point position
15
Conveyor Oven Time Monitor with Over-Heating Alarm
Description:
Anovenmonitordisplayingthetunneltimeinminutesandsecondsꢀ Thetunneltimeisdefined
as the time it takes for the heated object on the conveyor to travel from point A to point B in the
application diagram belowꢀ A visual indicator should activate if the tunnel time rises above a
preset limit of 22 minutes and 30 seconds which could cause overheating of the processed
materialꢀ The indicator should automatically reset when the tunnel time returns to the normal
operating rangeꢀ For ease of use, the display should be averaged over a period of 1 secondꢀ
Application Diagram:
Motor Control
Connect to
Coupling
A
B
Heat Source
Tunnel Oven
Coupling to
Chain Drive
Encoder
Gear Motor
ENTER
18:40
TACHOMETER
Drive Train Specs:
1250 RPM at non-reduced
motor shaft equates to
9 minutes and 15 seconds
of tunnel time
DTM8000 Meter
Wiring Diagram:
NC2
C2
Not Used
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
Not Used
Not Used
NO2
NC1
C1
Not Used
Not Used
Not Used
NO1
N
DTM8000-6
2 Amp
AC Line Input 85-265VAC, 50-60 Hz
L
}
COM
+5V
black
P1-9
red
P1-10
P1-11
P1-12
S1
S2
white
Encoder
Parameter Configuration:
Parameter
Value
2
Notes
10
20
Time Mode Setting
555
Display should indicate 9:15 (555) when motor at Reference RPM, parameter 21. In
time mode, all display values are entered in total number of seconds.
For example, 555 = (9 minutes * 60 seconds-per-minute) + 15 seconds.
This is the RPM at which the Display Reference, parameter 20, should be displayed.
Pulses per revolution of shaft encoder or pickup is 10 PPM
Display filtering / averaging set to 1 seconds
21
22
24
40
41
43
48
1250
10
1
4
Alarm active when display value is above upper limit
Constant alarm output with automatic reset
1
1
Flash display when alarm output is active
1350
Upper limit setting for 22 minutes and 30 seconds. In time mode, all limits are entered in
total number of seconds.
For example, 1350 = (22 minutes * 60 seconds-per-minute) + 30 seconds.
16
Take-up / Pay-out Reel Material Measurement with Alarm
Description:
A take-up / pay-out system where the DTM8000 displays a measurement of dispensed or
accumulated material in linear yardsꢀ Once the desired amount of material, 1500 yards,
hasbeendispensedoraccumulated, anexternallightshouldilluminatetoindicatethatthe
specifiedmaterialvolumehaspassedꢀ Atthispoint,theusermustbeabletopressabutton
on the user interface to reset the count to zero and the process repeatsꢀ
Application Diagram:
Capstan Drive Specs:
Capstan
Motor
28.3 Revolutions of the
Capstan motor equate to
50 linear yards of material
Belt
Speed Control
Pinch Rollers
Tension
Belt
Tension
Motor #1
Belt
Motor #2
Encoder
Tension
Tension
Torque
Control #2
Torque
Control #1
I
ENTER
3650
TACHOMETER
Pylon-Style
Illuminated
Alarm
DTM8000 Meter
Wiring Diagram:
120VAC
Illuminated
Pylon-Style
Alarm
NC2
Not Used
Not Used
Not Used
P1-1
C2
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
NO2
NC1
C1
Not Used
NO1
N
DTM8000-6
2 Amp
AC Line Input 85-265VAC, 50-60 Hz
L
}
COM
+5V
black
P1-9
red
P1-10
P1-11
P1-12
S1
S2
white
Not Used
Encoder
Attached to Driven
Capstan Pinch Rollers.
Parameter Configuration:
Parameter
Value
Notes
10
16
20
3
2
Up-Counter Mode Setting
Configure counter to reset on any button press
500
Display should increment 50 linear yards for each Reference Count, parameter 21.
Because the initial values were 28.3 revolutions per 50 linear yards, each is multiplied by
10 to give an even number to increase accuracy since the display can be programmed in
whole numbers.
21
283
In count mode, the Reference RPM is set in revolutions. 283 has been entered here to
represent 28.3 revolutions and the Display Reference has also been multiplied by 10 to
yield whole numbers.
22
40
41
42
48
10
4
Pulses per revolution of shaft encoder or pickup is 10 PPM
Alarm active when display value is above upper limit
Constant alarm output with manual reset required
No silencing, reset on any button press
2
1
1500
Upper limit setting for 1500 linear yards
17
Bi-directionalIncrementalPositionDisplay
Description:
A system is needed which will track the position of a bi-directional linear-motion platform
and allow the user to select a home or zero positionꢀ The display should read in inches
and indicate the position of the platform at all timesꢀ
Application Diagram:
Platform
Drive Train Specs:
40 Revolutions = 3.5 In.
of Platform Motion
Connect to
Coupling
Linear-Motion System
Coupling to
Chain Drive
Encoder
Gear Motor
ENTER
263.4
TACHOMETER
DTM8000 Meter
Motor Control
Wiring Diagram:
NC2
C2
Not Used
Not Used
Not Used
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P1-8
NO2
NC1
C1
Not Used
Not Used
Not Used
NO1
N
DTM8000-6
2 Amp
AC Line Input 85-265VAC, 50-60 Hz
L
}
COM
+5V
black
P1-9
red
P1-10
P1-11
P1-12
S1
S2
white
brown
Encoder
Parameter Configuration:
Parameter
Value
5
Notes
10
20
Up/Down Counter Mode
35
Because the initial values were 40 revolutions per 3.5 inches of platform motion, each is
multiplied by 10 to give an even number to increase accuracy since the display can be
programmed in whole numbers. Additionally, because of the decimal point position, the
Display Reference is multiplied by 10 to generate the proper display format. Without the
second multiplication by 10, the display would only read 3.5 inches when the drive motor
turned 400 revolutions.
21
400
In count mode, the Reference RPM is set in revolutions. 400 has been entered here to
represent 40 revolutions and the Display Reference has also been multiplied by 10 to yield
whole numbers.
22
25
10
3
Pulses per revolution of shaft encoder or pickup is 10 PPM
Decimal point position set to XXX.X on display
18
Troubleshooting
Problem
Possible Case
Solution
Display is blank
Power not applied
Using a volt meter, verify that a voltage between 85 and 265VAC is measured between
the L and N terminal block positions.
Contact technical support for additional help and instructions.
Defective unit
Display is dim
Display intensity
parameter is too low
Editing and increasing the display intensity parameter should cause the display digits to
become brighter.
When power is
applied, “LF-L” is
displayed
AC line supplying
power to unit has too
much noise
Review routing of power wires in machine to minimize electrical noise. Look for other
devices which share the same circuit which may be producing unacceptable levels of line
noise. In some applications, such as welding equipment, a careful regiment of applying
an AC line filter, re-routine wires, dividing circuits, using shielded cable, and properly
grounding devices will usually solve the problem.
AC line supplying
power to unit has an
abnormally low
frequency
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).
When power is
applied, “LF-H” is
displayed
AC line supplying
power to unit has too
much noise
Review routing of power wires in machine to minimize electrical noise. Look for other
devices which share the same circuit which may be producing unacceptable levels of line
noise. In some applications, such as welding equipment, a careful regiment of applying
an AC line filter, re-routine wires, dividing circuits, using shielded cable, and properly
grounding devices will usually solve the problem.
AC line supplying
power to unit has an
abnormally high
frequency
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).
The first or second Second alarm output
alarm output does parameters not
Second alarm output parameters not configured properly
Review alarm output #2 parameters. The first and second alarm relay outputs can be
tested by selecting the “Always On” value for the Activation Condition parameters for the
respective alarm output. When doing this, the relay click should be audible and the NC
(Normally Closed) and C (Common) terminals should become internally shorted at the
terminal block.
not seem to
function
configured properly
19
- Notes -
20
- Notes -
21
|